TY - JOUR TI - Performance analysis of thermal storage assisted cooling tower with night cooling AB - As global warming and water scarcity issues continue to grow, it is essential to increase resources efficiency for air conditionersand power plants. In order to increase the efficiency, the systems need to be modified to take the advantages of the low nighttemperature and thermal storage tanks. In this study, the low night temperature and thermal storage tanks effects on the coolingtower is studied using TRNSYS. Using a chiller operating from 8:00 to 16:00 as a case study, hot water from the condenser ispartially stored on daytime and cooled slowly during the night. The storage tank volume is optimized by considering two big tanksand five small tanks. The results show that night cooling reduces cooling water temperature by 5.8 °C or 21.8% while the coolingefficiency is increased by 36%. The thermal storage tanks enable to have the low continuous flow rate and help to reduce the fanpower by 67.1%. On the storage side, compared to two tanks system, the tanks volume is reduced by 16.5% when 5 tanks are used.In theory this reduction can go up to 50% by increasing the number of tanks and reducing their individual size. AU - OUEDRAOGO, Kiswendsida AU - TOPRAK, KASIM DO - 10.2339/politeknik.517603 PY - 2020 JO - Politeknik Dergisi VL - 23 IS - 4 SN - 1302-0900 SP - 1027 EP - 1035 DB - TRDizin UR - http://search/yayin/detay/423371 ER -